Instrument Type |
Minimum Range |
Resolution |
Remarks |
1 |
Tacometer |
0 to 5000 rpm |
± 2% of reading |
± 5 rpm |
|
2 |
Temperature Measurement Air Immersion Contact |
-40 to 240 oF |
± 1% of reading |
0.2 oF |
|
3 |
Avometer |
0 to 600 VAC 0 to 100 Amps |
± 2% of reading |
1.0 Volt 0.1 Ampere |
|
4 |
Micro manometer (DP-Calc) |
0 to 10.00 in.w.g. |
± 2% of reading |
0.01 in.w.g. <1in.w.g.0.1in.w.g. >1in.w.g. |
|
5 |
Rotating Vane |
50 to 2500 fpm |
± 5% of reading |
20 fpm |
|
6 |
Humidity Measurement |
10 to 90% RH |
2% RH |
1% |
|
7 |
Direct Reading Hood |
100 to 2000 cfm |
± 5% of reading,± 5 cfm |
Digital – 1 cfm |
|
8 |
Pitot Tubes (2 required) |
18” minimum, adequate length for intended use. |
N/A |
N/A |
|
9 |
Hydronic Differential Pressure Measurement (Hydronic Manometer) |
0 to 100 in.w.g. 0 to 100 ft.w.g. |
± 2% of reading |
1.0 in.w.g. |
|