Standard Instrument Requirements:

# Instrument Type Minimum Range Resolution Remarks
1 Tacometer 0 to 5000 rpm ± 2% of reading ± 5 rpm  
2 Temperature Measurement Air Immersion Contact -40 to 240 oF ± 1% of reading 0.2 oF  
3 Avometer 0 to 600 VAC 0 to 100 Amps ± 2% of reading 1.0 Volt 0.1 Ampere  
4 Micro manometer (DP-Calc) 0 to 10.00 in.w.g. ± 2% of reading 0.01 in.w.g. <1in.w.g.0.1in.w.g. >1in.w.g.  
5 Rotating Vane 50 to 2500 fpm ± 5% of reading 20 fpm  
6 Humidity Measurement 10 to 90% RH 2% RH 1%  
7 Direct Reading Hood 100 to 2000 cfm ± 5% of reading,± 5 cfm Digital – 1 cfm  
8 Pitot Tubes (2 required) 18” minimum, adequate length for intended use. N/A N/A  
9 Hydronic Differential Pressure Measurement (Hydronic Manometer) 0 to 100 in.w.g. 0 to 100 ft.w.g. ± 2% of reading 1.0 in.w.g.